Set the signal type and the range of the instrument, then type any one of the signal, the percent, the real value or the PLC counts. The others fill in. Example: a 4-20 mA level transmitter on a 22 ft tank reads 12 mA at 50%, which is 11 ft.
1. The instrument range
2. Convert
Type in any box. The others update.
Points along the range
| Percent | Signal | Value | Counts |
|---|
The same point in every signal type
Useful for matching a 0-10 V input to a 4-20 mA output, or the other way around.
| Signal type | At this point |
|---|
Loop resistor (mA to volts)
A precision resistor turns a current loop into a voltage. 250 ohms turns 4-20 mA into 1-5 V.
Loop power check
Does the supply have enough voltage at 20 mA?
Tank level to pressure
For a pressure transmitter at the bottom of an open tank. Use this to find the pressure range to set for the tank height.
4-20 mA to PSI converter
A pressure transmitter spreads its range across 4 to 20 mA. On a 0 to 100 psi transmitter, 4 mA is 0 psi and 20 mA is 100 psi. Change the range to match your device.
Steps
- The range is set to 0-100 psi. Change the real values at 0% and 100% to match your transmitter.
- Type the mA reading to see psi, or type psi to see the mA.
- Use the counts box if you need the value your PLC card reports.
Example
On a 0-100 psi transmitter, 12 mA is 50 psi, 8 mA is 25 psi, and 16 mA is 75 psi.
Questions
- How do I find psi from mA?
- psi = (mA - 4) / 16 x range. On a 0-100 psi device at 10 mA, that is 6 / 16 x 100 = 37.5 psi.
- Is that gauge or absolute?
- It follows the transmitter. A gauge transmitter reads gauge pressure and an absolute one reads absolute.